Wednesday, January 2, 2019

January 02, 2019

No-Load Transformer And Its Phasor Diagram

Before we start discussing about the no-load condition of a transformer, it is important to first understand that what is meant by no-load.
"A transformer is said to be on no-load when the secondary winding of the transformer is left open-circuited thereby reducing the secondary current to zero".

WHAT HAPPENS WHEN TRANSFORMER IS AT NO-LOAD?

During no-load condition, secondary current in the transformer reduces to zero and when an alternating voltage is applied to the primary, a small current I0 flows in the primary winding.
The current I0 is called no-load current of the transformer and it is 3 to 5 percent of the rated primary current.
No-load current is made up of two components Iu and Im.
Iu is called magnetizing component.It magnetizes the core. We can also say that it sets up the flux in the core and therefore Im is in phase with (flux). It is also called reactive or wattless component of no-load current.
The other component Iw supplies the hysteresis and eddy-current losses in the core. It is in the phase with the applied voltage V1. It is also called active or wattful component of no-load current.

Phasor Diagram At No Load

Phasor diagram for a transformer(real) under no-load condition is shown in the fig. below.

The flux  is taken as the reference phasor.  The magnetizing component of the no-load current Im, magnetizes the core i.e, it sets up the flux in the core. Therefore, Im is in phase with the flux.
Iw is in phase with the applied volage, V1.  The phasor sum of Im and Iw is I0. The angle 0, between Iw and I0 is called no-load power factor angle. The power factor on no load is cos(0).
Iw = I0 . cos(0).
Im = I0 . cos(0)
I0 = v{(Iw) + (Im)}
Since, E1 and E2 are induced by the same flux ?, therefore E1 and E2 will be in same phase , but E1 and E2 lags behind the flux ? by 90 degree. E1 = k. E2 (where k = T1/T2,  T1 & T2 are no. of turns on primary and secondary winding)
E1 and V1 will be opposite to each other due to Lenz Law. If the voltage drop in the primary winding are neglected then V1 will be equal and opposite to the E1.
Power input to the transformer during no-load condition is :-
P0 = V1 . I0. cos (0)

Wednesday, August 15, 2018

August 15, 2018

Sumpner's test or Back-to-Back test on Transformer

In this post we will study about the Sumper's test on a transformer. It is also called Regenerative test or Back-to-Back test.
Please read the whole article carefully for understanding it properly
Main objective of the Sumper's test is to check the transformer efficiency , maximum temperature rise. It is also used to measure the losses in the large transformers.  This method is advantageous for large  transformers because for full load test on large transformers, it would be expensive as a large amount of energy will get wasted during the test. Therefore, large transformers can be tested by Sumper's test.
Sumper's test requires requires two identical transformers. Given figure shows the circuit diagram for back-to-back test (Sumper's test).
Regenerative test of transformer , back to back test of transformer
The primary winding of the  two transformers are connected in parallel and is supplied at rated voltage and frequency. As seen in the figure, a Voltmeter, an ammeter and watt meter are connected to the input.
The secondary of the transformers are connected in series in phase opposition and voltmeter is connected across them. The range of the voltmeter is twice the voltage of secondary winding. Phase opposition of the winding is checked by this voltmeter. If voltmeter reads 0, it means they are in phase opposition , because both windings have equal voltages but in opposite direction due to which overall voltage in the secondary circuit become 0.
Now if the supply is given to the primary circuit, then the total voltage in secondary circuit will be 0, as discussed above.
There will be no current in the secondary winding and it will behave as secondary is open circuited. Only No-load current will flow in the primary circuit which is measured by the ammeter on the primary side.
Hence , watt meter on the primary side will read the total Iron losses of the both transformers.
Now, a small voltage is injected in the secondary circuit with the help of regulating transformer (see the figure). The magnitude of the voltage is adjusted till the ammeter on the secondary side reads the full-load secondary current. This produces the full load copper losses of the both transformers. Thus watt meter on the secondary side reads the total Full-load copper losses.
Thus with the help of this method we have founded the both losses in the transformer. We have loaded the transformer to the full load but the power taken from the supply is just that it will be only sufficient to supply the losses of both transformers.

Thursday, June 21, 2018

June 21, 2018

Transformer - Introduction & Basic

What is an electrical transformer? 
An electrical transformer is a static device which consists of two stationary electrical circuits connected to each other by a common magnetic circuit for the purpose of transferring electrical energy between them.
This transfer of electrical energy takes place without the change in frequency.
Transformer works on the principle of Electromagnetic Induction. Electromagnetic Induction is one of the basic law of Electrical Engineering. You can read about Electromagnetic Induction.

CONSTRUCTION & WORKING PRINCIPLE  OF TRANSFORMER

A simple transformer consists of two coils wounded on a core as shown in the figure.

There is no electrical connection between these two coils.
When an alternating voltage source V is applied to the coil 1, an alternating current I1 flows in it. This alternating current produces an alternating magnetic flux in the core. This alternating flux links with the turns  T1 of the coil 1 and induces an emf E1 by self-induction.
Thus, all the flux produced by the coil 1 also links with the turns T2 of the coil 2 and thereby inducing an emf E2 by mutual induction.
If load is connected to the coil 2, then an alternating current I2 will flow through it and hence electrical energy will delivered to the load without change in frequency.
Coil 1 which receives the electrical energy from the source of a.c supply is called primary winding.
Coil 2 which is connected to the load and delivers the energy to the load is called secondary winding.
Note that the transformer can only work with the alternating source. It cannot be used for transferring electrical energy in DC form because transformer works on the principle of Electromagnetic Induction and it requires that current should be alternating in nature. So, transformer cannot work on DC.

EMF EQUATION OF THE TRANSFORMER

As we have studied that an emf is induced in both the coils or windings. So the magnitude of the emf can be calculated from the emf equation of the transformer which is ;
E = 4.44* fi * f * T
Where , E = Magnitude of emf induced.
             fi = Maximum flux in Weber.
             f  = Frequency in Hertz.
             T = Number of turns in the coil.
With the help of the emf equation, emf induced in the primary as well as secondary winding can be calculated by providing the suitable number of turns.
It shows that winding having higher number number of turns will have higher voltage and hence it is called high voltage  (hv) winding.
Winding having lower number number of turns will also have lower voltage is called low voltage (lv) winding.

TRANSFORMATION RATIO

The ratio of emf induced in the primary winding to the emf induced in the secondary winding is called transformation ratio. It is denoted by 'k'.
k = E1/E2 = T1/T2
Transformation ratio can also be defined as the ratio of number of turns of primary winding and number of turns of secondary winding. It is also called turn ratio.

STEP-UP & STEP-DOWN TRANSFORMER

Transformer in which the secondary voltage is greater than the primary voltage is called step-up transformer.
Step-up transformer has turn ratio smaller than 1.
Transformer in which the secondary voltage is smaller than the primary voltage is called step-down transformer.
Step-down transformer has turn ratio greater than 1.
Transformer having secondary voltage equal to the primary voltage is called isolation transformer or one-to-one transformer.
Such transformer has turn ratio equal to 1.